Permit: T09EL02178

Parcel: 116141700

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
11/30/2009 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
11/25/2009 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) EXPOSED CONDUCTORS BEHIND PANEL, SHOULD BE IN RACEWAY
2) STRAP #4 BARE TO WALL
3) VERIFY WATER PIPE BOND
4) MUST USE A LISTED RISER SUPPORT ON ROOF. HOMEMADE OUT OF SMASHED EMT CONDUIT NOT APPROVED