Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2009 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 11/25/2009 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) EXPOSED CONDUCTORS BEHIND PANEL, SHOULD BE IN RACEWAY 2) STRAP #4 BARE TO WALL 3) VERIFY WATER PIPE BOND 4) MUST USE A LISTED RISER SUPPORT ON ROOF. HOMEMADE OUT OF SMASHED EMT CONDUIT NOT APPROVED |