Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/07/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 10/06/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOND SERVICE NIPPLE 2) SUPPORT CONDUITS AT SIDES OF PANEL AND ABOVE 3) USE APPROVED FITTINGS WITH LB'S 4) INSTALL MAIN BONDING JUMPER 5) SEAL ENTRANCES ABOVE CURRENT CARRING PARTS 6) USE LISTED SPLICES FOR ALUMINUM CONDUCTORS 7) WHERE IS NEW GROUNDING ELECTRODE SYSTEM ? 8) RECEPTACLE BELOW PANEL TO BE PER 406.8 9) NEED PERMANENT METAL ADDRESS LABEL ON METER ? 10) CANNNOT USE DRYWALL SCREWS FOR MOUNTING HARDWARE 11) WHERE IS GAS BOND |