Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/28/2009 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
10/16/2009 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUND RODS TO BE MINIMUM 6' FROM OTHER GROUND RODS
2) GROUNDING ELECTRODES AT BLDG TO BE BONDED TOGETHER TO FORM GROUNDING ELECTRODE SYSTEM
3) GAS AND WATER FOR EACH UNIT TO BE BONDED TO SERVICE FOR THAT UNIT
4) CANNOT HAVE BREAKER POSITIONS HIGHER THAN 6'-7"
5) EXPLAIN 50 AMP CIRCUIT FOR DRYER
6) SEAL OPENING AT CABLE ENTRY WITH NON COMBUSTIBLE MATERIAL
7) ARE COPPER AND ALUMINUM CONDUCTORS SPLICED TOGETHER
8) WHERE IS GROUNDED (NEUTRAL) CONDUCTOR FOR SUB PANEL
9) LUG IN PANEL NOT LISTED FOR 2 WIRE TERMINATION
10) THIS WRITE UP IS FOR 321 & 323
11) GROUND PHONE AND CABLE SYSTEMS