Permit: T09EL02162

Parcel: 107082450


Addresses:

720 W ALTURAS ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/27/2009 ELECTRIC - FINAL Approved
10/26/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
USE PROPER CIRCUIT BREAKERS
SEE NOTE #2
09/28/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EQUIPMENT GROUND FOR 30 AMP CIRCVUIT TO BE MINIMUM #10, SEE NEC 250.122 (DRYER)
2) INSTALL BREAKERS LISTED FOR USE IN MURRAY PANEL
3) INSTALL PROTECTIVE BUSHING ON CONNECTOR AT ROMEX ENTRY
4) CONNECT EQUIPMENT GROUND TO 6 X 6 JUNCTION BOX WHERE HAVE SPLICES
5) GROUND PHONE SYSTEM. CONNECT PHONE BOX TO BLDG
6) EXPLAIN 60 AMP BREAKER FOR RANGE CIRCUIT, SEE NEC 210