Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/27/2009 | ELECTRIC - FINAL | Approved | ||
| 10/26/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* USE PROPER CIRCUIT BREAKERS SEE NOTE #2 |
|
| 09/28/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EQUIPMENT GROUND FOR 30 AMP CIRCVUIT TO BE MINIMUM #10, SEE NEC 250.122 (DRYER) 2) INSTALL BREAKERS LISTED FOR USE IN MURRAY PANEL 3) INSTALL PROTECTIVE BUSHING ON CONNECTOR AT ROMEX ENTRY 4) CONNECT EQUIPMENT GROUND TO 6 X 6 JUNCTION BOX WHERE HAVE SPLICES 5) GROUND PHONE SYSTEM. CONNECT PHONE BOX TO BLDG 6) EXPLAIN 60 AMP BREAKER FOR RANGE CIRCUIT, SEE NEC 210 |