Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/02/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/30/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH #3 PREVIOUS INSPECTION-PANEL 'A' 2) NOTE: MAIN PANEL IS DISCONNECT |
|
| 09/24/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FILL UNUSED OPENINGS IN PANELS 2) LABEL OUTSIDE COVERS OF PANELS 3) SEPERATE GROUNDS AND NEUTRALS AT SUB PANELS 4) USE BREAKERS LISTED FOR USE BY MANUFACTURE 5) RE-TIGHTEN ALUMINUM CONDUCTORS 6) PRESENT OBJECTIONABLE CURRENT AND PARALLEL PATHS AT SERVICE 7) IDENTIFY CIRCUITS AND RE-LABEL PANEL DIRECTORY 408.4 8) RE-ATTACH BOX TO WALL AND INSTALL GFI RECEPTACLE ON BACK WALL |