Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/28/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/26/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL NEUTRAL CONDUCTOR TO SUB PANEL FEED TO BE IDENTIFIED WITH WHITE CONDUCTOR ALONG ENTIRE LENGTH 2)MIN SIZE EQUIPMENT AROUND FOR 60 AMP FEED TO #10. USE #10 TO BOND METAL JUNCTION BOX. 3) COMMPER ALUMINUM CONDUCTORS CANNOT BE SPLICED TOGETHER. DISSIMILAR METALS |
|
| 10/22/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* GATE LOCKED MESSAGE SAID TO USE GATE IN ALLEY |
|
| 10/08/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK GROUND RODS 2) OK GAS AND WATER BOND 3) RECALL AFTER SWING OVER IS COMPLETE |