Permit: T09EL02122

Parcel: 134243330


Addresses:

901 S COLGATE DR

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
10/14/2009 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
09/17/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HAVE EXPOSED WIRING @ GARAGE DOOR INSTALLED IN JUNCTION BOX AND INSTALL BLANK
2. CLOSE OPEN JUNCTION BOX @ FRONT PORCH
3. INSTALL SMOKE DETECTORS IN BEDROOMS PER INSTRUCTIONS
4. BATHROOM RECEPTACLE TO BE GFCI PROTECTED
5. VERIFY ALL KITCHEN COUNTER RECEPTACLES ARE GFCI
6. INCANDESCENT CLOSET LIGHTS TO BE 100% ENCLOSED OR REMOVED & BLANKED.
7. INSTALL MAIN BONDING JUMPER IN SERVICE PANEL.
8. BOX EXPOSED WRONG @ GARAGE MAN DOOR
9. GARAGE RECEPTACLES TO BE GFCI PROTECTED
10. HAVE EXPOSED WIRING HANGING IN GARAGE CORRECTED.
11. CLOSE OPEN KNOCK-OUTS @ DISCONNECTS IN GARAGE. CHECK FOR PROPER OVER-CURRENT PROTECTION & GROUNDING OF ENCLOSURES.
12. CHECK 3-PRONG RECEPTACLES HAVE EQUIPMENT GROUNDS. IF NOT, THEY NEED TO BE GFCI PROTECTED OR INSTALL 2 PRONG RECEPTACLES.
13. HAVE A QUALIFIED ELECTRICAL CONTRACTOR MAKE REPAIRS & THOROUGHLY CHECK HOUSE WIRING.