Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/21/2009 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 10/14/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 10/09/2009 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* | |
| 09/17/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RESUPPORT SUB-PANEL TO WALL, ALSO ISOLATE NEUTRAL & GROUNDS, ALSO PANEL NOT GOUNDED AND IN VIOLATION OF DEDICATED CLEARANCE. 2. INTALL SMOKE DETECTORS IN BEDROOMS, 110-26 NEZ 3. I.D. BOTH UNITS, 2 METERS & SERVICES ADD 2ND UNIT TO PERMIT 4. INSTALL GHI PROTECTED RECEPTS AT KITCHEN SINKS. 5. EXPOSED & UNSUPPORTED RONEX IN KITCHEN OF MAIN HOUSE, WIRING NOT TO CODE IN DINING AREA. |