Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/14/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LIGHT FIXTURE IN CARPORT MISSING COVER AND SUPPORTN FLEX PER CODE 2) INSTALL SMOKE DETECTORS IN BEDROOMS 3) ELECTRIC SERVICE IN NEED OF UPGRADE: NOT GROUNDED PER CODE, INDOOR RATED MAIN SERVICE DISCONNECT HAS WATER DAMAGE (RUST), MULTI TAPPED (3) ON LOAD TERMINALS NOT ALLOWED, BARE OR DAMAGED LOAD CONDUCTORS DUE TO WEATHER AND SECOND DISCONNECT UNDER MAIN DISCONNECT NOT TO CODE 4) REVISE THIS PERMIT TO INCLUDE SERVICE UPGRADE AND RECALL INSPECTION WHEN READY 5) WORK TO BE DONE BY LICENSED OR QUALIFIED ELECTRICIAN |