Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09EL02072
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/05/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
12/31/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NEED TO DO ITEMS ON LIST 2) CALL BACK FOR FINAL |
|
12/24/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY MARK |
|
09/25/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL MISSING OUTDOOR LIGHT FIXTURES 2) REMOVE NON-CODE COMPLIANT WIRING AND RECEPTACLE TO TREE IN FRONT YARD 3) INSTALL MISSING DEVICE WALL PLATES 4) INSTALL SMOKE DETECTORS IN BEDROOMS AND INSTALL NEW SMOKE DETECTOR IN HALL. INSTALL PER INSTRUCTIONS 5) HAVE EXPOSED WIRES HANGING FROM CEILINGS AND FROM CEILING FANS. MAKE SAFE AND CLOSE UP BOXES 6) VERIFY PERMIT FOR NEW WATER HEATER, NOT INSTALLED PER CODE 7) KITCHEN COUNTER RECEPTACLES TO BE GFI PROTECTED 8) CHECK WIRING IN GARAGE AND WORK SHOP HAVE OPEN SPLICES, OPEN JUNCTION BOXES. REMOVE OR MAKE CODE COMPLIANT 9) OUTDOOR RECEPTACLES TO BE GFI PROTECTED 10) TIME LOCK NOT WIRED PER CODE 11) MISSING DEAD FRONT ON PANEL 12) VERIFY 3 PRONG RECEPTACLES AND HAVE EQUIPMENT GROUND 13) CLEAN UP PANEL WIRE PER CODE 14) HAVE ELECTRICAL CONTRACTOR GO THRU ENTIRE HOME, MAKE CORRECTIONS AND CHECK WIRING 15) TOO MANY VIOLATIONS TO LIST |