Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - RECONNECT
Permit Number - T09EL02040
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/16/2009 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* | |
09/16/2009 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
09/09/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. OUTDOOR RECEPTACLE TP BE GFI PROTECTED 2. ALL KITCHEN COUNTER RECEPTACLE TO BE GFI PROTECTED 3. BATHROOM RECEPTACLES TO BE GFI PROTECTED 4. INSTALL SMOKE DETECTORS IN BEDROOMS. REPLACE HALL SMOKE DETECTOR. INSTALL PER INSTRUCTIONS. |