Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 09/17/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/04/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) KITCHEN COUNTER RECEPTACLES TO BE GFI PROTECTED 2) BATHROOM RECEPTACLES TO BE GFI PROTECTED 3) INSTALL SMOKE DETECTORS IN BEDROOMS PER INSTRUCTIONS 4) HALL SMOKE DETECTOR TO BE BE OPERATIONAL 5) CEILING FAN IN BEDOOM NOT WORKING PER CODE. INSTALL PER CODE OR REMOVE FAN AND WIRING 6) INCANDESCENT CLOSET LIGHT TO BE 100 PERCENT ENCLOSED 7) HAVE 3 PRONG GROUNDING TYPE RECEPTACLES ON 2 WIRE UNDERGROUNDED SYSTEM. TO BE GFI PROTECTED OR 2 PRONG RECEPTACLES INSTALLED 8) HAVE QUALIFIED ELECTRICAL CONTRACTOR MAKE CORRECTIONS THEN RESCHEDULE WHEN COMPLETE |