09/03/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL PROTECTIVE BUSHING ON ENDS OF EMT WHERE WIRES ENTER
2. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL
3. STRAP EMT TO WITHIN 3' OF CONNECTIONS
4. BENDS ON 3/4" EMT HAVE REDUCED INTERNAL DIAMETER
5. CANNOT USE WHITE CONDUCTORS IN RACEWAY AS PHASE CONDUCTORS
6. INSTALL SEALING WASHERS AT CONDUIT ENTRY IN TOP OF PANEL OR INSTALL MEYERS HUBS
7. WILL NEED PERMIT FOR NEW WATER HEATER
8. EXPOSE GROUND RODS
9. LUG IN SERVICE PANEL NOT LISTED FOR 2 WIRE TERMINATION