Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T09EL02003
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/03/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL PROTECTIVE BUSHING ON ENDS OF EMT WHERE WIRES ENTER 2. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL 3. STRAP EMT TO WITHIN 3' OF CONNECTIONS 4. BENDS ON 3/4" EMT HAVE REDUCED INTERNAL DIAMETER 5. CANNOT USE WHITE CONDUCTORS IN RACEWAY AS PHASE CONDUCTORS 6. INSTALL SEALING WASHERS AT CONDUIT ENTRY IN TOP OF PANEL OR INSTALL MEYERS HUBS 7. WILL NEED PERMIT FOR NEW WATER HEATER 8. EXPOSE GROUND RODS 9. LUG IN SERVICE PANEL NOT LISTED FOR 2 WIRE TERMINATION |