Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/18/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
09/18/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/01/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEAL OPEN KNOCKOUTS IN FAN BOXES
2) CONNECT EQUIPMENT GROUND TO METAL FAN BOX
3) INSTALL CONNECTOR ON ROMEX TO FAN BOXES
4) BLANK OPEN FAN BOXES
5) INSTALL MISSING RECEPTACLE PLATE
6) REMOVE OR INSTALL IN JUNCTION BOX CIRCUIT CONDUCTORS TO SPA