Permit: T09EL01935

Parcel: 116210080


Addresses:

53 S GRANDE AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/16/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/09/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
09/29/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SPOKE WITH ELECTRICAL CONTRACTOR FOR JOB. HE HAS NO KNOWLEDGE OF WORK PERFORMED
2) ELECTRICAL WIRING HAS BEEN ADDED TO THIS PERMIT
A) BOXES MORE THAN 1/4" 314.20
B) USE APPROVED SPLICE CONNECTORS WITH GROUND CONDUCTORS
C) OPEN WALL ABOVE SUB PANEL TO INSPECT CABLES
3) FINISH PREVIOUS ITEMS 1, 3, 6 & 9
09/21/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) NEED ANTI-TIP FOR RANGE
2) WATER HEATER NEEDS DISCONNECTING MEANS AND USE APPROVED FITTINGS
3) BOND GAS FOR THIS SERVICE
4) FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON COMBUSTIBLE PRODUCT
5) SEPERATE GROUND AND NEUTRALS AT SUB-PANEL
6) SECURE CABLES AT TOP OF PANEL
7) PLEASE VERIFY PERMIT FOR NEW WIRING TO INTERIOR
8) FEEDER CONDUCTORS UNDER SIZED
9) PLEASE VERIFY QUALIFIED ELECTRICIAN DOING WORK
08/24/2008 ELECTRIC - FINAL Denied 1) POST ADDRESS ON BLDG
2) PLEASE VERIFY PERMITS FOR NEW WORK TO INTERIOR
3) CLOSET LIGHTS NOT PER 410.8
4) INSTALL SMOKE DETECTOR PER INSTRUCTIONS
5) CONDUIT CIOUPLING BROKEN
6) SECURE CODUIT TO STRUCTURE ALSO GROUNDING ELECTRODE CONDUCTOR
7) VERIFY GAS AND WATER BOND
8) LABEL DISCONNECT
9) USE PROPER OVER CURRENT FOR CONDUCTORS
10) METER 110 SERVICE 220