Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/16/2009 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 10/15/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE PROTECTION FOR CABLES ABOVE PANEL FOR 2" EXPOSED BELOW CEILING |
|
| 10/13/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANNOT SHAVE OFF STRANDS OF CABLE TO MAKE FIT IN GROUND BAR-USE APPROVED LUG SIZED FOR CONDUCTORS IN SUB PANEL 110.3 2) SHEET METAL PROTECTION FOR CABLES MUST BE 1/16" THICK MIN. 300.4 NEC 3) SEE NOTES 1, 2B AND 3 |
|
| 10/09/2009 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection :* 1) PROTECT CABLES UNDER DRYWALL 2) FINISH 2B, 5 AND 6 OF PREVIOUS INSPECTIONS |
|
| 09/29/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/21/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/24/2008 | ELECTRIC - RECONNECT | Denied |