Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) ITEMS ON LIST OK |
|
| 08/21/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) USE APPROVED FITTINGS FOR CARFLEX 110.3 NEC 2) GROUNDING ELECTRODE SYSTEMS TO BE COMMON BOTH SERVICES PER 250.58 NEC 3) USE APPROVED ROOF JACK FOR CONDUIT PENETRATIONS THRU ROOF 4) SERVICES RE-ENERGIZED PRIOR TO INSPECTION APPROVALS |