Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/28/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) MET ALEX AND DISCUSSED PROBLEMS |
|
| 12/20/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BREAKERS FOR #8 NM WRONG SIZE 2) DERATE PER 310.15 3) NEED DISCONNECTING MEANS FOR WATER HEATERS 4) WHERE IS DISCONNECT FOR REAR WEST A/C UNIT ? 5) PLEASE PROVIDE LADDER FOR ACCESS TO ATTIC 6) FINISH PREVIOUS ITEMS 2, 3 & 6 |
|
| 08/24/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SPLIT SYSTEM ALL A/C NEEDS DISCONNECTING MEANS INTERIORS 2) BOXES OVER FILLED ATTIC AND UNDER FLOOR 3) LABEL A/C AS TO SERVICE 4) ALL KITCHEN RECEPTS TO BE GFCI PROTECTED 210.8 5) WINDOW A/C PLUGED INTO AN EXTENSION CORD 6) SUPPORT EMT CONDUITS 7) EXPOSED NM CABLE KITCHEN |
|
| 02/18/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK UNIT PANELS AND BUSHINGS TO BE RE-SECURED IN 2" CONDUITS 2) NEED ELECTRIC CONTRACTOR ON SITE TO WALK THRU WIRING METHODS USED TO RE-WIRE UNITS 3) RECALL INSPECTION-WAITED TILL 8:00 AM |