Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) STRAP RISER TO STRUCTURE 2) NEED LISTED MAST BRACE KIT 3) TIGHTEN LOOSE FITTINGS 4) ONLY ONE NEUTRAL TO A TERMINAL LUG CONNECTION 5) NEED NEW GROUNDING ELECTRODE SYSTEM-RODS, GAS AND WATER BONDS 6) FULLY IDENTIFY UNGROUNDED CONDUCTORS 7) BOXES AND FITTINGS TO BE FOR WET LOCATION 8) REPAIRS TO BE MADE BY 9/1/09 |