Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/29/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FOR RESIDENTIAL RECONNECT |
|
| 09/21/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 08/20/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* INTERIOR: 1. WE HAVE GROUNDED RECEPTACLES ON UNGROUNDED CIRCUITS 2. NEED SMOKE DETECTORS AS PER MANUFACTURERS INSTRUCTIONS IN BEDROOMS 3. ATTACH LIGHT FIXTURES TO BOX IN WALL 4. BATHROOM RECEPTACLES TO BE GFCI 5. PLEASE VERIFY CEILING BOXES RATED FOR FANS 6. INSTALL RECEPTACLES AND BOXES CORRECTLY 7. COOLER SWITCH CANNOT BE INSTALLED IN DUCT WORK 8. PROPER WIRING METHODS FOR CLOSET LIGHT NEEDED ALSO, KITCHEN LIGHTING, MICROWAVE 9. PLEASE VERIFY NEW PLUMBING AND AC PERMITS 3. |
|
| 08/19/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COULD NOT UNDERSTAND CODE FOR LOCK BOX 2) LOCKED-NO ACCESS EXTERIOR: 1) RECEPTACLE NOT INSTALLED TO WALL-ALSO NEEDS BOX 2) DRYER RECEPTACLE TO BE FOR WET LOCATION 3) TIGHTEN LOOSE FITTINGS FOR CONDUIT |