Permit: T09EL01888

Parcel: 136282730


Addresses:

7615 E PERSIMMON DR

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/25/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED OUTSIDE LIGHT FRONT AND BACK
2) OPEN SPLICES, BOXES AND CONDUCTORS HIDDEN IN WALL
3) OUTDOOR RECEPTACLES TO BE FOR WET LOCATION
4) FRAMING FOR BEARING AND NON BEARING WALL NEED PERMIT
5) PLUMBING, HEATING AND COOLING NEED PERMIT
08/21/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
INTERIOR ONLY:
1) ZIP CORD WIRING TO FIXTURE TO BE REMOVED-ALL
2) CABINET WIRING NOT TO CODE
3) BACK ROOM WIRING NOT TO CODE
4) KITCHEN AND BATHROOM RECEPTACLES TO BE GFCI PROTECTED
5) SMOKE DETECTORS NEEDED FOR BEDROOMS-NOT HEAT DETECTORS
6) PLEASE VERIFY PERMITS FOR CLOSET ADDITION, WATER HEATER AND BACKROOM
7) MISSING PLUMBING FIXTURES AND HEATING UNIT
8) NEED #9 PREVIOUS INSPECTION
08/19/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
1) REMOVE NON-CODE COMPLIANT WIRING AT CARPORT AND FRONT OF HOUSE
2) INSTALL MISSING LIGHT FIXTURE AT FRONT DOOR
3) OUTDOOR RECEPTACLES TO BE GFI PROTECTED
4) NEED PANEL DIRECTORY
5) SEAL OPEN BREAKER POSITIONS IN SERVICE PANEL
6) SEAL OPEN KNOCKOUTS IN PANEL
7) NEED TO VERIFY PERMITS FOR ADDITON TO BACK OF HOUSE AND WORK SHOP ADDITION
8) THIS INSPECTION WAS OUTSIDE ONLY, UNABLE TO GAIN ACCESS TO INTERIOR
9) HAVE QUALIFIED ELECTRICAL CONTRACTOR GO THRU PROPERTY AND REMOVE/REPAIR ALL NON-CODE COMPLIANT WIRING
10) NOT A COMPLETE INSPECTION