Permit: T09EL01886

Parcel: 132110150


Addresses:

2118 E 36TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
11/25/2009 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
11/23/2009 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1) NO ONE ANSWERS DOOR
2) NO AVAILABILITY FOR PHONE ANSWER
11/20/2009 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) NM SHEATHING NOT TO BE IN CEMENT
2) SEPERATE GROUNDS AND NEUTRALS AT SUB PANELS
3) USE CORRECT SIZE BREAKER FOR AMPACITY
4) SECURE PANELS IN WALL
5) FINISH GROUNDING
11/19/2009 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) M/C CABLE NOT FOR OUTDOORS
2) USE APPROVED CONNECTORS
3) FILL UNUSED OPENINGS IN PANEL
4) CUT BACK BOLTS IN PANEL
5) JUNCTION BOX TO BE FOR WET LOCATION
6) LABEL CIRCUIT BREAKERS
7) FINISH GROUNDING H20 AND GAS
8) LINE TO INTERIOR IS A FEEDER OF #12 AND #10 TO SUB PANEL, 5-20 AMP CIRCUITS CONNECTED SIZE FEEDER AND BREAKER TO CODE
11/18/2009 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
11/17/2009 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
BOTH UNITS:
1) COMPLETE GROUNDING
2) BRACE RISER
3) SUPPORT RISERS WITH 1/4 BOLTS, NO DRYWALL SCREWS
4) CANNOT SHARE NEUTRAL ON TWIN CIRCUIT BREAKER
5) CANNOT INSTALL OVER GAS METERS