Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/25/2009 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 11/23/2009 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1) NO ONE ANSWERS DOOR 2) NO AVAILABILITY FOR PHONE ANSWER |
|
| 11/20/2009 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) NM SHEATHING NOT TO BE IN CEMENT 2) SEPERATE GROUNDS AND NEUTRALS AT SUB PANELS 3) USE CORRECT SIZE BREAKER FOR AMPACITY 4) SECURE PANELS IN WALL 5) FINISH GROUNDING |
|
| 11/19/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) M/C CABLE NOT FOR OUTDOORS 2) USE APPROVED CONNECTORS 3) FILL UNUSED OPENINGS IN PANEL 4) CUT BACK BOLTS IN PANEL 5) JUNCTION BOX TO BE FOR WET LOCATION 6) LABEL CIRCUIT BREAKERS 7) FINISH GROUNDING H20 AND GAS 8) LINE TO INTERIOR IS A FEEDER OF #12 AND #10 TO SUB PANEL, 5-20 AMP CIRCUITS CONNECTED SIZE FEEDER AND BREAKER TO CODE |
|
| 11/18/2009 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* | |
| 11/17/2009 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* BOTH UNITS: 1) COMPLETE GROUNDING 2) BRACE RISER 3) SUPPORT RISERS WITH 1/4 BOLTS, NO DRYWALL SCREWS 4) CANNOT SHARE NEUTRAL ON TWIN CIRCUIT BREAKER 5) CANNOT INSTALL OVER GAS METERS |