Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/10/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 02/05/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) PROTECT CONDUCTORS AT FITTING BACK OF PANEL 300.4 2) PVC CONDUIT ON SIDE OF HOUSE TO BE SUPPORTED 3) PVC CONDUIT NOT ALLOWED MORE THAN 360 DEGREE IN A RUN 4) ABOVE GRADE TO BE SCHEDULE 80 5) NEED A DISCONNECT AT A/C 6) TIGHTEN BOND CLAMP SCREWS 7) ENERGIZED WITHOUT CLEARANCE |