Permit: T09EL01860

Parcel: 138050300

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
02/10/2010 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
02/05/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) PROTECT CONDUCTORS AT FITTING BACK OF PANEL 300.4
2) PVC CONDUIT ON SIDE OF HOUSE TO BE SUPPORTED
3) PVC CONDUIT NOT ALLOWED MORE THAN 360 DEGREE IN A RUN
4) ABOVE GRADE TO BE SCHEDULE 80
5) NEED A DISCONNECT AT A/C
6) TIGHTEN BOND CLAMP SCREWS
7) ENERGIZED WITHOUT CLEARANCE