Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/08/2009 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 09/01/2009 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) STILL NEED TO SEAL OPENING AT BACK PANEL WITH NON-COMBUSTIBLE MATERIAL 2) STILL NEED TO REMOVE OR CORRECT UNSAFE ELECTRIC OUTDOORS 3) RECALL WHEN COMPLETE |
|
| 08/28/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUND RODS TO BE MINIMUM 6' APART 2) GAS PIPE BOND TO BE CONNECTED TO BAR METAL 3) INSTALL ROOF JACK 4) SEAL OPENING AT WIRE ENTRY WITH NON COMBUSTIBLE MATERIAL 5) HAVE 14 AWG WIRE ON 20 AMP BREAKERS 6) NEED PANEL DIRECTORY 7) MINIMUM CLEARANCE FOR SERVICE CONDUCTORS OVER RESIDENTIAL PROPERTY TO BE 12' 8) HAVE NUMEROUS OUTDOOR ELECTRIC THAT IS UNSAFE NEEDS TO BE CORRECTED OR REMOVED. ROMEX NOT TO BE INSTALLED OUTDOORS IN WET LOCATION 9) RECALL WHEN READY 10) USE LISTED MAST BRACING |
|
| 08/20/2009 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* | |
| 08/19/2009 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY GEORGE THE HOMEOWNER |