Permit: T09EL01850

Parcel: 136160380


Addresses:

8325 E LOUISE DR

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/08/2009 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
09/01/2009 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) STILL NEED TO SEAL OPENING AT BACK PANEL WITH NON-COMBUSTIBLE MATERIAL
2) STILL NEED TO REMOVE OR CORRECT UNSAFE ELECTRIC OUTDOORS
3) RECALL WHEN COMPLETE
08/28/2009 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUND RODS TO BE MINIMUM 6' APART
2) GAS PIPE BOND TO BE CONNECTED TO BAR METAL
3) INSTALL ROOF JACK
4) SEAL OPENING AT WIRE ENTRY WITH NON COMBUSTIBLE MATERIAL
5) HAVE 14 AWG WIRE ON 20 AMP BREAKERS
6) NEED PANEL DIRECTORY
7) MINIMUM CLEARANCE FOR SERVICE CONDUCTORS OVER RESIDENTIAL PROPERTY TO BE 12'
8) HAVE NUMEROUS OUTDOOR ELECTRIC THAT IS UNSAFE NEEDS TO BE CORRECTED OR REMOVED. ROMEX NOT TO BE INSTALLED OUTDOORS IN WET LOCATION
9) RECALL WHEN READY
10) USE LISTED MAST BRACING
08/20/2009 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
08/19/2009 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1) CANCELLED BY GEORGE THE HOMEOWNER