Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/19/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) LOCKED-NO ACCESS 2) POWER HAS BEEN CLEARED UNDER PERMIT #T09EL01807. PLEASE RECALL TOGETHER AFTER CROSS OVER AND CORRECTIONS COMPLETED |
|
| 08/11/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PANEL: 1) PROTECT CONDUCTORS FROM SHARP METAL EDGES AT BACK OF PANEL 2) ONLY ONE CONDUCTOR PER TERMINAL LUGS 3) BREAKERS TO BE LISTED FOR USE BY MANUFACTURE 4) MAIN BREAKER BACK FEED NEEDS MANUFACTURES HOLDOWN 5) USE CORRECT AMPACITY BREAKER FOR #8 NM CABLE AND FULLY IDENTIFY UNGROUNDED CONDUCTOR 6) CONDUCTORS NOT MAKED PER CODE 7) GROUND RODS TO BE MINIMUM 6' APART 8) PLEASE VERIFY GAS AND WATER BONDS INTERIOR: 1) GROUNDED RECEPTACLES ON UNGROUNDED SYSTEM 2) CLEAN EXCESS PAINT FROM DEVICES 3) NEED SMOKE DETECTORS IN BEDROOMS 4) USE APPROVED CORD FOR WALL A/C 5) OPEN JUNCTION BOX |