Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/16/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/23/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK ELECTRICAL CHANGE OVER 2) PATCH ROOF WHERE EXISTING RISER CONDUIT WAS REMOVED 3) RECALL FINAL WHEN DONE |
|
| 08/20/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NEUTRAL IS BONDED AT SERVICE DISCONNECT INSTALL GROUND BAR IN SUB PANEL TO ISOLATE NEUTRALSFROM EQUIP. GROUNDS, 250-6 & PLUG HOLE IN ROOF OVERHANG LEFT FROM REMOVED RISER CONDUIT |
|
| 08/12/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CALLED INTO DENISE AT TEP 9:58 AM 2) CALL FOR FINAL INSPECTION AFTER CUT OVER |