Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/16/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/23/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK ELECTRICAL CHANGE OVER 2) PATCH ROOF WHERE EXISTING SERVICE RISER WAS REMOVED 3) RECALL FINAL INSPECTION WHEN DONE |
|
| 08/20/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 2" CONDUIT CONNECTOR TO CLOSE TO TOP OF SUB-PANEL, COVER MUST OPEN PROPERLY 90 DEGREES AS MANUFACTURED. NEUTRAL IS BONDDED AT SERVICE DISCONNECT - MUST ISOLATE GROUNDS & NEUTRALS IN SUB-PANEL PER 250-6, 250-24-A1 & 250-24-5. |
|