Permit: T09EL01797

Parcel: 11302054L

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/16/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/23/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK ELECTRICAL CHANGE OVER
2) PATCH ROOF WHERE EXISTING SERVICE RISER WAS REMOVED
3) RECALL FINAL INSPECTION WHEN DONE
08/20/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
2" CONDUIT CONNECTOR TO CLOSE TO TOP OF SUB-PANEL, COVER MUST OPEN PROPERLY 90 DEGREES AS MANUFACTURED.
NEUTRAL IS BONDDED AT SERVICE DISCONNECT - MUST ISOLATE GROUNDS & NEUTRALS IN SUB-PANEL PER 250-6, 250-24-A1 & 250-24-5.
08/12/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CALLED INTO DENISE AT TEP 9:58 AM
2) CALL FOR FINAL INSPECTION AFTER CUT OVER
3) REPAIR BROKEN LOCK TAB ON LOAD SIDE COVER