Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/12/2009 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 08/10/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) FINISH #2,6,7 & 11 FROM PREVIOUS INSPECTION 2) FINISH #2 OF INSPECTION 8/4/09 |
|
| 08/07/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BREAKER TO BE LISTED FOR USE BY MANUFACTURE 2) USE CORRECT AMPACITY BREAKER FOR #NM CABLE 3) NEED ANTI OXIDE COMPOUND WITH ALUMINUM CONDUCTORS 4) PROPERLY SUPPORT RISER 5) A ROOF JACK IS NEEDED FOR ROOF PENETRATION 6) PLEASE VERIFY SUN LIGHT RESISTANT MARKINGS PER CONDUCTORS 7) NEW NM CABLE IN JUCNTION BOX 8) A PERMANENT METAL ADDRESS LABEL IS NEEDED 9) BREAKERS WILL NEED TO BE LABELED 10) NEED GAS AND WATER BONDS 11) PLEASE VERIFY QUALIFIED ELECTRICIAN PERFORMING WORK |
|
| 08/04/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE MISSING PARTS-NO UPGRADE WORK DONE 2) PLEASE VERIFY PERMITS FOR NEW WORK TO INTERIOR |