Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/28/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/15/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) NO WORK PROGRESS |
|
| 08/07/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BREAKER SIZES TO LARGE FOR CONDUCTOR AMPACITY 2) NEW PANEL NEED PERMIT FOR UPGRADE 3) NUMEROUS VIOLATIONS AT NEW PANEL TO LIST 4) ALL RECEPTACLES IN BATHROOM TO BE GFI PROTECTED 5) PLEASE VERIFY QUALIFIED ELECTRICIAN PERFORMING WORK |
|
| 08/04/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) UNIT LOCKED, NO ACCESS 2) USE APPROVED DEAD FRONT |
|
| 07/31/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING DEAD FRONT ON PANEL 2) BATHROOM RECEPTACLE TO BE GFI PROTECTED 3) KITCHEN COUNTER RECEPTACLE TO BE FFI PROTECTED 4) INSTALL SMOKE DETECTORS IN BEDROOMS AND ONE OUTSIDE BEDROOM PER INSTRUCTIONS 5) RECALL WHEN READY |