Permit: T09EL01767

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09EL01767

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/10/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) WIRING FOR NEW CEILING FANS HAS BEEN REMOVED
2) ALL OTHER PREVIOUS INSPECTION ITEMS CORRECTED
08/06/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
1) GATE/BLDG LOCKED
08/04/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUNDING ELECTRODE CONDUCTOR MUST HAVE IRREVERSABLE SPLICE, CRIMP OR X-WELD. MECH LUG NOT APPROVED
2) VERIFY WATER AND GAS BONDING
08/03/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CALLED INTO KATHY AT TEP 10:12 AM
2) INFORMED OWNER THAT A PERMIT IS REQUIRED FOR INTERIOR ADDITION OF NEW CEILING FANS AND WIRING
3) FINAL INSPECTION FOR THIS PERMIT WILL NOT BE APPROVED UNTIL PERMIT OBTAINED