Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2009 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* 1) ITEMS ON LIST OK |
|
| 08/21/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO PUT PROPER CONNECTOR FOR CABLE IN 3/4 EMT 2) NEED PROPER NIPPLE FOR LP'S NOT CHASE NIPPLE |
|
| 08/12/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE WIRES 3/0 CU OK 2) NEED TO REMOVE EMT AND WIRES FROM TOP OF PANEL THAT AREA IS DEDICATED SPACE FOR EXPOSED BUSS BARS ONLY |