Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T09EL01766

Parcel: 110091210


Addresses:

2861 N ROSEMONT AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/25/2009 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
1) ITEMS ON LIST OK
08/21/2009 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TO PUT PROPER CONNECTOR FOR CABLE IN 3/4 EMT
2) NEED PROPER NIPPLE FOR LP'S NOT CHASE NIPPLE
08/12/2009 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SERVICE WIRES 3/0 CU OK
2) NEED TO REMOVE EMT AND WIRES FROM TOP OF PANEL THAT AREA IS DEDICATED SPACE FOR EXPOSED BUSS BARS ONLY