| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/06/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ALL SWITCHES, OUTLETS AND FIXTURES EXPOSED 2) NO NEW WIRING FOUND, REPLACEMENT OF OUTLETS, SWITCHES AND LIGHT FIXTURES ONLY |
|
| 08/03/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NOTES 2,3,4,1 & 5 2) GFCI PROTECT EXTERIOR OUTLET 3) NEW DUCT WORK AND A/C ROOF TOP GAS PACK REQUIRES PERMITS 4) NEW PLUMBING TO KITCHEN AND BATHS REQUIRES PERMITS 5) WATER HEATER EXTEND RELIEF LINE TO EXTERIOR 6) ACORN CLAMPS GROUND ROD SYSTEM 7) EXPOSE 1 OUTLET AND SWITCH IN EACH ROOM |
|
| 07/30/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE VERIFY PERMITS FOR NEW INTERIOR REMODEL 2) EXPOSED NM CABLE ON EXTERIOR WITH BOXES WITH UNUSED OPENINGS 3) FILL UNUSED OPENINGS AT SIDEVENTS? 4) BREAKER TO BE AS PER MANUFACTORS REQUIREMENTS 5) NOT ALL CIRCUITS CONNECTED 6) STRAP SEAL TITE TO WALL & TIGHTEN FITTINGS 7) VEEND? 2ND GROUNDING ELECTRODE |