Permit: T09EL01749

Parcel: 12914004B


Addresses:

702 E 36TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09EL01749

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/25/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/21/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
MAIN SERVICE:
1) POST ADDRESS ON STREET SIDE OF BLDGS
2) PROVIDE EVIDENCE OF 25 OHMS OR LESS OR PROVIDE 2ND SUPLIMENTAL GROUNDING ELECTRODE
2ND STRUCTURE:
1) NEED MAIN DISCONNECTING MEANS 225.31
2) PROVIDE EVIDENCE OF 25 OHMS OR LESS
3) BOND PANEL 250.58
4) FILL UNUSED OPENINGS IN BACK OF PANEL WITH A NON COMBUSTIBLE PRODUCT
5) NEED GAS AND WATER BONDING
08/14/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The inspector was unable to locate the job.| 945*
1) CANNOT LOCATE-POST ADDRESS