Permit: T09EL01720

Parcel: 131020950


Addresses:

5409 E 26TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
09/29/2009 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
1) CALL FOR ELECTRIC FINAL AFTER POWER IS RESTORED
07/27/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ONE (120V SINGLE CIRCUIT) TIED INTO A TWO POLE 20/20 AMP BREAKER REQUIRES ON SINGLE POLE BREAKER
2) ONE 20 AMP CIRCUIT GOING UP TO ROOF EXPOSED ENTERS CONDUIT
3) TAPED SPLICE IN SERVICE PANEL, USE WIRE NUT
4) SMOKE DETECTORS REQUIRED IN ALL BEDROOMS
5) GFCI RECEPTS REQUIRED KIT COUNTER TOP RECEPTS AND BATHROOM
6) COOLER EXPOSED ROMEX IN CLOSET, TAPE HOLDING RECEPT BOX IN PLACE
7) INSTALL 2 PRONG RECEPTS, WHERE 3 HOLE RECEPTS (WITH GRD HAVE BEEIN INSTALLED)
8) UNABLE TO LOCATE GRD SCREW FOR BONDING GRD/NEUTRALS AT SERVICE PANEL
9) A/C UNIT WEST PLUG IN CONNECTION NEED HARD WIRE WITH CORRECT SIZE BREAKER