Permit Number - T09EL01704

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
08/07/2009 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
07/23/2009 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1) NEED 2 GROUND RODS 6' APART OR MORE
2) NEED LIST KIT FOR BRACING RISER
3) NEED WATER AND GAS BONDING
4) NEED STRAPPING FOR 1 1/2 TO SUB PANEL
5) NEED TO FIX METER BASE HINGES