Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) METER SECTION SEALED WITHOUT INSPECTION 2) SERVICE ENERGIZED WITHOUT APPROVAL 3) GROUNDED CONDUCTOR TO BE IDENTIFIED PER NEC 200.6 AND 200.7 4) EXPOSE GROUND RODS 5) BOND GAS AND WATER PIPING 6) PROVIDE 6' LADDER FOR ACCESS TO BELL BOXES 7) EXPLAIN WIRES HANGING OUT OF HOUSE TO RIGHT OF PANEL 8) NEED PROPER WORKING CLEARANCES IN FRONT OF PANEL NEC 110.26 9) ALL EXISTING CIRCUITS WHERE 20 AMP ? 10) REMOVE EXTENSION CORD RUNNING ACROSS ROOF 11) OUTDOOR RECEPTACLES TO BE GFI PROTECTED 15A & 20A 120V |