Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2009 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 10/02/2009 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) BREAKERS TO BE LISTED FOR USE BY MANUFACTURE 2) ONLY ONE CONDUCTOR TO ACORN CLAMP 3) FINISH #3 & 5 PREVIOUS INSPECTIONS |
|
| 08/11/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO PERMITS ON RECORD FOR NEW WORK TO INTERIOR 2) NO FURTHER INSPECTIONS UNTIL PERMITS FOR INTERIOR OBTAINED |
|
| 08/07/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) PLEASE VERIFY PERMITS FOR WORK TO INTERIOR 2) HIGHTEST BREAKER POSITION NO HIGHER THAN 6'-7" 3) SEAL ENTRANCES WITH APPROVED FITTING ABOVE CURRENT CARRING PARTS 4) SUPPORT PVC AT SIDE OF PANEL 5) IS THIS AN HIGH LEG PANEL ? 6) NO CIRCUITS CONNECTED AT THIS TIME 7) PLEASE VERIFY 2ND GROUND ROD, WATER AND GAS BONDS |