08/20/2009 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
1) ALL ITEMS ON LIST OK
08/18/2009 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL LISTED MAST BRACING CANNOT USE SMASHED EMT
2) USE ANTI-OXIDATION COMPOUND AT ALUMINUM CONNECTIONS
3) SEAL OPENINGS AT WIRE ENTRY BACK OF PANEL WITH NON-COMBUSTIBLE MATERIAL
4) RECALL WHEN READY
5) SERVICED ENERGIZED PRIOR TO APPROVAL