Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/20/2009 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* 1) ALL ITEMS ON LIST OK |
|
| 08/18/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL LISTED MAST BRACING CANNOT USE SMASHED EMT 2) USE ANTI-OXIDATION COMPOUND AT ALUMINUM CONNECTIONS 3) SEAL OPENINGS AT WIRE ENTRY BACK OF PANEL WITH NON-COMBUSTIBLE MATERIAL 4) RECALL WHEN READY 5) SERVICED ENERGIZED PRIOR TO APPROVAL |