Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/22/2009 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 07/20/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) GROUNDING EQUIPMENT CONDUCTOR TO BE GREEN ENTIRE LENGTH IN RACEWAY 250.119 2) GENERAL LABELING OR ABREVIATIONS FOR PANEL DIRECTORY NOT ALLOWED 408.4 3) BOX OVER FILLED |