Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/30/2009 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1. PROPER INSTALL ? JUMPER FOR WATER PIPE 2. USE APPROVAL STRIP FOR SERVICE MUST USE MIN1/2' HARDWARE ( STAINLESS STEEL) CANNOT USE ROCK SCREWS 3. RECALL AFTER SWING OPEN COMPLETE |
|
| 07/22/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE CONDUCTORS TO BE INSTALLED 2) SECURE MAST TO BLDG 3) SECURE PANEL TO BLDG 4) BOND GAS AND WATER 5) COMPLETELY DRIVE GROUND RODS AND USE CLAMPS FOR DIRECT BURY 6) SERVICE MAST TO BE BONDED PER NEC 250. 7) NEED PROPER WORKING CLEARANCE IN FRONT OF SERVICE 8) SERVICE MAST TO BE RIGID OR IMC CONDUIT NOT EMT 9) HAVE QUALIFIED ELECTRICAL CONTRACTOR COMPLETE WORK |