Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/22/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLETE ALL PREVIOUS INSPECTION ITEMS 2) WEATHER HEAD HAS COME APART, YOU HAVE CONDUCTORS UP AGAINST METAL THIS IS HAZARDOUS SITIUATION AND NEEDS TO BE ADDRESSED PROMPTLY 3) HAVE OPEN SPLICE ON ROOF. CORD TO SWAMP COOLER TO BE REPLACED 4) INSTALL WALL PLATES 5) CAONNOT OPEN PANEL PAINTED OVER. SEAL OPEN BREAKER POSITIONS. LABEL CIRCUITS AND REMOVE PAINT 6) KITCHEN COUNTER RECEPTS TO BE GFI 7) WATER HEATER NEEDS T & P LINE 8) INTALL SMOKE DETECTORS IN BEDROOMS AND OUTSIDE BEDROOMS. INSTALL PER INSTRUCTIONS 9) HAVE QUALIFIED ELECTRICAL CONTRACTOR MAKE CORRECTIONS & GO THRU ENTIRE UNIT AND CORRECT ALL ELECTRICAL HAZARDS |