Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T09EL01628

Parcel: 134113560


Addresses:

948 S SARNOFF DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/04/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/14/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TO PULL PERMIT FOR NEW ROOF TOP A/C UNIT. PROVIDE COPY AT NEXT INSPECTION
2) REMOVE BUSH FROM IN FRONT OF PANEL, WORKING CLEARANCE NEC 110.26
3) SERVICE CONDUCTORS NOT SIZED PROPERLY, TO BE SIZED FOR 200 AMP SERVICE NEC 310
4) INSTALL BREAKERS LISTED FOR USE IN CUTLER HAMMER PANEL
5) EXPOSE GROUND RODS
6) HAVE CUT STRANDS ON FEEDER CABLE TO SUB PANEL
7) BOND WATER AND GAS PIPING NEC 250.104
8) PROPERLY IDENTIFY EQUIPMENT GROUND TO NEW A/C UNIT NEC 250.119