Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/14/2010 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) CLEAN SURFACE UNDER GROUND LUG 250.12 2) INSULATE NEUTRAL CONDUCTOR IN JUNCTION BOX |
|
| 01/06/2010 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 01/05/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WORKING CLEARANCES 110.26 2) PLEASE VERIFY WHO IS QUALIFIED ELECTRICIAN 3) A REFEE MAY BE ASSESSED |
|
| 12/29/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) A LISTED MAST BRACE IS NEEDED AND SECURED TO A JOIST 2) FINISH #1 (110.26) AND #2 |
|
| 12/23/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) MAINTAIN WORKING CLEARANCES 110.26 2) RISER HARDWARE TO BE 1/4" MIN 3) HIGHEST AVAILABLE BREAKER NOT TO BE OVER 6' 7" 4) FILL UNUSED PORTION OF OPENING WITH APPROVED FITTING 5) SECURE BONDING CONDUCTOR AND BURY 6) DRIVE GROUND RODS FLUSH 7) PLEASE IDENTIFY GROUNDED CONDUCTOR CLOSER TO WEATHER HEAD 8) VERIFY ROOF JACK INSTALLATION 9) MAINTAIN CLEARANCE ACROSS ROOF |