Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/07/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 08/20/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PERMIT AND METERS TO BE PROPERLY ADDRESSED. NEED TO REVISE PERMIT FOR BOTH ADDRESSES 2) INSTALL GROUNDING ELECTRODE SYSTEM AND BOND GAS & WATER PIPING 3) PANEL DIRECTORIES NEEDED 4) STAP EMT WITHIN 3' OF CONNECTIONS 5) USE LOCK NUT WITH CHASE NIPPLES 6) GROUNDS AND NEUTRALS TO BE SEPERATE AT SUB PANELS 7) NO DBL TAPPING OF BREAKERS UNLESS ALLOWED BY INSTRUCTIONS 8) 100 AMP BREAKERS IN SERVICE PANEL NOT LISTED FOR SIZE WIRE TERMINATED ON BREAKER. HAVE CUT STRANDS 9) HAVE IMPROPER JUMPERING OF METAL SOCKET 10) WHERE DOES 2 1/2 UNDERGOUND RACEWAY GO ? 11) INSTALL EQUIPMENT ? WITH FEEDER 12) INSTALL G.E. BREAKERS IN G.E. PANEL 13) WAS UNDERGROUND RACEWAY INSPECTED ? 14) SERVICE CONDUCTOR NOT SIZED PROPERLY FOR 200 AMP SERVICE 15) OBTAIN SERVICES OF QUALIFIED ELECTRICAL CONTRACTOR |