Permit: T09EL01592

Parcel: 118081290


Addresses:

923 W 25TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/07/2010 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
08/20/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PERMIT AND METERS TO BE PROPERLY ADDRESSED. NEED TO REVISE PERMIT FOR BOTH ADDRESSES
2) INSTALL GROUNDING ELECTRODE SYSTEM AND BOND GAS & WATER PIPING
3) PANEL DIRECTORIES NEEDED
4) STAP EMT WITHIN 3' OF CONNECTIONS
5) USE LOCK NUT WITH CHASE NIPPLES
6) GROUNDS AND NEUTRALS TO BE SEPERATE AT SUB PANELS
7) NO DBL TAPPING OF BREAKERS UNLESS ALLOWED BY INSTRUCTIONS
8) 100 AMP BREAKERS IN SERVICE PANEL NOT LISTED FOR SIZE WIRE TERMINATED ON BREAKER. HAVE CUT STRANDS
9) HAVE IMPROPER JUMPERING OF METAL SOCKET
10) WHERE DOES 2 1/2 UNDERGOUND RACEWAY GO ?
11) INSTALL EQUIPMENT ? WITH FEEDER
12) INSTALL G.E. BREAKERS IN G.E. PANEL
13) WAS UNDERGROUND RACEWAY INSPECTED ?
14) SERVICE CONDUCTOR NOT SIZED PROPERLY FOR 200 AMP SERVICE
15) OBTAIN SERVICES OF QUALIFIED ELECTRICAL CONTRACTOR