Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T09EL01585
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/07/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CLOSE OPEN BREAKER POSITIONS IN PANEL COVER 2) NEED PANEL DIRECTORY 3) BOND WATER AND GAS PIPING 4) EXPLAIN INSTALLED BAR AT BOTTOM OF PANEL, NOT PART OF MANUFACTURERS PANEL INSTALL 5) NEED 2 GROUND RODS MINIMUM 6' APART 6) EXPLAIN ALL NEW ROMEX CABLES INSTALLED INTO PANEL AND ALL NEW WORK NEEDS PLAND & PERMITS 7) SEAL OPENING IN BACK OF PANEL AT WIRE ENTRY WITH NON COMBUSTIBLE MATERIAL 8) BOND NIPPLE BETWEEN METER & PANEL AND BOND RISER 9) VERIFY PERMITS FOR NEW WATER HEATER AND ROOF TOP A/C UNIT 10) RECALL WHEN READY 11) SERVICE ENERGIZED WITHOUT APPROVAL 12) CALLED KATHY AT TEP NOT AWARE OF SERVICE UPGRADE AT THIS ADDRESS |