Permit: T09EL01565

Parcel: 118036770


Addresses:

2060 S CERRO DR


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09EL01565

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/07/2010 ELECTRIC - FINAL Approved NOT IN CODE COMPLIANCE
12/01/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HAZARDOUS CONNECTION 12-2 ROMEX ADDED AT PANEL REQUIRES PROTECTION FROM PHYSICAL DAMAGE, PROVIDE PROPER CONNECTOR AT PANEL
2) NUMEROUS ADDITIONS ADDED TO PROPERTY TO INCLUDE GARAGE ENCLOSURE TO FAMILY ROOM WITH FIREPLACE, REAR ADDITION 10" X 20' ATTACHED PORCHES TO SOUTH END, 20' X 20' RAMADA AT REARY YARD WITH ELECTRICAL, STORAGE ROOM AT NORTH END WITH ELECTRICAL. PROVIDE PROOF OF PERMIT FOR ALL ADDITIONS OR OBTAIN PROPER PERMITS AND INSPECTIONS FOR EACH OR RETURN TO PERMITTED STATE
3) GFCI PROTECT KITCHEN COUNTER OUTLETS
4) SMOKE ALARAMS REQUIRED ALL BEDROOMS
5) 15 DAY TEMP POWER ALLOWED
11/30/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ACCESS 9:10 AM
07/02/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) POST HOUSE NUMBERS VISIBLE FROM STREET
2) PROVIDE PROOF OF PERMIT GARAGE INTO ROOM WITH FIREPLACE. PORCH ATTACHED SOUTH WALL. RAMADA AT REAR WITH ELECTRICAL
3) DBL LUGGED BREAKERS IN PANEL
4) PROVIDE PROOF OF PERMIT ATTACHED STORAGE ROOM NORTH WALL WITH ELECTRICAL AND REAR ROOM ADDITION ATTACHED TO WEST WALL
5) SMOKE ALARM BEDROOMS
6) GFCI PROTECT KITCHEN OUTLETS
7) OMIT OUTLET AT BREAKFAST BAR COUNTER OVER 6"