Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
Permit Number - T09EL01541
Inspection Description - ELECTRIC - FINAL
Inspection Status - Not ready for Inspection
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/07/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CARPORT LIGHT WIRE MUST BE IN CONDUIT UP TO BIRD BOARD AREA 2) RECALL FOR ELECTRIC FINAL WHEN CORRECTION IS MADE AND AFTER POWER IS RESTORED |
|
| 06/29/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POST STREET ADDRESS 2) PROPERLY TERMINATE WATER HEATER CONNECTION 3) WATER HEATER T/P LINE MUST RUN DOWN HILL 4) ALL EXPOSED 120 VOLT WIRING BELOW 8' AFF OR GRADE MUST BE PROTECTED. EXTERIOR LIGHTS AND FANS 5) AFTER RECONNECT, ALL KITCHEN COUNTER RECEPTACLES MUST BE TESTED FOR GFI PROTECTION |