Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09EL01511
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/06/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
12/23/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
11/30/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED LETTER FROM TEP FOR METTER ISSUE |
|
09/18/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) ELECTRICAL DONE IN UNIT 035 IS OK 2) NEED TO SEE UFER AND METER PROBLEM RESOLVED 3) CALL BACK FOR FINAL |
|
09/02/2009 | ELECTRIC - FINAL | Denied | UFER MISSING HAVE 7 METERS AND ONLY 6 ALOUD ITEMS ON LIST OK |
|
08/25/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO BOND SERVICE AND SUB PANEL 2) NEED BOND BUSHING ON SUB PANEL 2" & 3/4 3) NEED SEAL UP OPENING ON BOTTOM OF SUB PANEL 4) NEED TO STRAP FLEX ON BOTTOM OF SUB PANEL AND CLEAN IT 5) NEED SCREW ON DEAD FRONT ON SUB PANEL |
|
08/24/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |