Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2009 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 06/26/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GFCI PROTECTED OUTLETS REQUIRED IN KITCHEN AND BATHROOMS 2) ALL EXPOSED ROMEX WIRE UNDER 8' FROM FIN. FL. SHALL BE PROTECTED 3) PVC AND ABS PIPE NOT ALLOWED FOR ELECTRICAL WIRE CHASE 4) BEND ON SERVICE ENTRANCE CABLE TO TIGHT 10 DIA. MIN. REQUIRED 5) UPGRADE PERMIT REQUIRED 6) VERIFY DET GARAGE TO REAR IS PERMITED APPROVED 7) VACUUM BREAKERS REQUIRED ON EXT. HOSE BIBS 8) GLASS IN BATHRROOM WINDOW SHALL BE TEMPERED 9) SMOKE ALARMS MISSING IN BEDROOMS AND HALLWAY 10) HAVE LICENSED ELECTRICIAN CHECK ALL ELECTRIC FOR COMPLIANCE |