Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2011 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 11/22/2011 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/24/2009 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY DIANE |
|
| 06/29/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE ROMEX AT CARPORT 2) CIRCUITS, KIT AND BATHROOMS (RECEPTACLES) TO BE GFCIC PROTECTED-SEE HANDOUT FROM CITY 3) ALL BEDROOMS TO HAVE EMERGENCY EGRESS TO OUTSIDE 4) PROBLEM LIVING CEILING, POSSIBLE BROKEN RAFTER 5) SMOKE DETECTORS REQUIRED (SEE HANDOUT) 6) ALL ELECTRIC FIXTURES TO BE IN PLACE 7) WILL CALL TEP REF. LOCK ON SERVICE PANEL 8) HOUSE MUST BE READY TO OCCUPY, OR YOU NEED TO GET REPAIR PERMIT TRY FOR CONSTRUCTION POWER 9) REMOVE TAPE FROM GAS FLUES, H20 HTR AND FURNACE 10) SHOWER NOT BUILT TO CODE, RESEARCH REQUIRED |